Download Product documentation

Transcript
Software "DALI Gateway IC00P01DAL"
Functional description
i As part of device assignment during DALI commissioning (online), single-battery-operated
DALI emergency lights must always be assigned to planned single devices (single
addressing) provided that these operating devices are to execute an emergency light
function. Assignment to group-related single devices (group addressing) of offline
commissioning is possible, however, only with the limitation that these operating devices
can only be used for standard lighting control (if supported by the operating device) and not
for emergency lighting applications.
i The DALI short addresses are always assigned in the parameter configuration of the single
devices and can thus be influenced. With the addition of group and device names, unique
naming of DALI operating devices is possible in this way. Through the transmission of the
unique names to the KNX building visualisation (e.g. control panels), the user is able particularly during error diagnosis - to identify the lighting components easily.
Page 158 of 218