Download Product documentation

Transcript
Software "DALI Gateway
IC00P01DAL" Object table
Function:
Object
h
1532
Description
Function:
Object
h
1533
Description
Function:
Object
h
1534
Description
Function:
Object
h
1535
Description
Collective feedback
Function
Feedback switching status
Name
Collective
feedback groups
1-16
Type DPT
4 byte 27.001
Flag
C, -, (T),
(R)1
4-byte object for collective feedback of individual switching states. The
collective feedback summarises the switching status of the DALI groups 1...16
in just one telegram. The object contains bit-orientated feedback information of
these individual groups.
This object is only visible if the addressing type set in the ETS allows for group
control.
Collective feedback
Function
Feedback switching status
Name
Collective
feedback groups
17-32
Type DPT
4 byte 27.001
Flag
C, -, (T),
(R)1
4-byte object for collective feedback of individual switching states. The
collective feedback summarises the switching states of the DALI groups
17...32 in just one telegram. The object contains bit-orientated feedback
information of these individual groups.
This object is only visible if the addressing type set in the ETS allows for group
control 1-32.
Collective feedback
Function
Feedback switching status
Name
Collective
feedback single
devices1-16
Type DPT
4 byte 27.001
Flag
C, -, (T),
(R)1
4-byte object for collective feedback of individual switching states. The
collective feedback summarises the switching status of the DALI single
devices 1...16 in just one telegram. The object contains bit-orientated
feedback information of these single devices.
This object is only visible if the addressing type set in the ETS allows for single
device control.
Collective feedback
Function
Feedback switching status
Name
Collective
feedback single
devices17-32
Type DPT
4 byte 27.001
Flag
C, -, (T),
(R)1
4-byte object for collective feedback of individual switching states. The
collective feedback summarises the switching states of the DALI single
devices 17...32 in just one telegram. The object contains bit-orientated
feedback information of these single devices.
This object is only visible if the addressing type set in the ETS allows for single
device control.
1: The communication flags are set automatically depending on the configuration. "T" flag for
active object; "R" flat for passive object.
Page 33 of 218