Download Transition from MELSEC-A/QnA (Large Type), AnS
Transcript
2 REPLACEMENT OF MELSECNET (II) AND MELSECNET/B (PLC TO PLC For MELSECNET/H normal station 1Ns1 that is gateway station, change the settings of MELSECNET II 2-tier first half/second half settings by: • Dividing the data into the first half and second half and refreshing them by the setting of "Refresh parameters"*1 Also, for MELSECNET/H control station 2Mp3 of gateway station, change the settings of MELSECNET II 3-tier first half/second half settings by: • Assigning LB/LW (first + last size) to each station by the setting of "Network range assignment (Common parameters)"*2 • Dividing the data into the first half and second half and refreshing them by the setting of "Refresh parameters"*1 MELSECNET/H network 1 Normal station 1Ns1 CPU MELSECNET/H network 2 Control station 2Mp3 Common parameters B/W LB/LW 0 100 0 100 1Mp3 180 200 200 280 LB/LW 1Mp3 1Mp3 2Mp3 2Mp3 2Ns1 2Ns2 1Ns2 1Ns1 380 400 Empty 1Mp3 500 500 580 600 600 1Ns2 680 6FF 0 100 2Mp3 180 1Mp3 2Mp3 280 300 2Ns1 380 2Ns2 480 400 4FF 2Mp3 2Ns1 2Ns2 1Ns2 77F 1FFF 1FFF 1FFF Link refresh *1 Set not to duplicate B/W on the CPU. *2 Perform the LB/LW assignment for network 2 control station 2Mp3 including the same LB/LW area as that of 1Mp3 to relay network 1 control station 1Mp3. 2 - 56