Appendix A Addressing Figure A.11 illustrates addressing 4 modules, each with the same I/O group number, but in four different racks of a single I/O chassis. (This method is explained in Figure A.11.) Figure A.11 Group Address of a Module in Four Different Racks I/O Group No. Rack 1 03 Rack 2 47 03 Rack 3 47 03 Rack 4 47 03 47 Í Input Rack I/O Group 1 I/O Group 1 I/O Group 1 I/O Group 1 Address 111 Address 121 Address 131 Address 141 I/O Group NOTE: When addressing a one-block transfer module, it must be addressed by the lowest group number that it occupies and at slot 0. For example, a one-slot block transfer module in rack 1, group 2 and 3 (chassis slot 2) would be addressed (by Rack-Group-Slot) at location 120. NOTE: When addressing a two-slot block transfer module, it too must be addressed by the lowest group number that it occupies and at slot 0. For example, a two-slot block transfer module in rack 3, groups 4, 5, 6, and 7 (it occupies chassis slots 3 and 4) would be addressed (by Rack-GroupSlot) at location 340. Also see the appropriate block transfer module user’s manual. Block Transfer modules must be located in the same slot pair (i.e., slots 0/1, 2/3, A15