Download Momentum - LUCKINSlive
Transcript
EMC Measures for the Communications Adapter Central Discharge Function for the PROFIBUS DP Central Discharge Function Each cable shield should be galvanically grounded with the earth using FE/PE grounding clamps immediately after the cable has been connected to the cabinet. Static Discharge In the case of a very long bus cable, which has been installed but not yet connected, you must discharge the static as follows: Step 1 Action Select the PROFIBUS DP connector closest to the FE/PE grounding clamp. 2 Touch the metal of the connector housing to the cabinet’s FE/PE grounding clamp to carry out a static discharge. 3 Now connect the bus connector to the device. 4 Discharge the other PROFIBUS DP cable connectors as described in steps 2 and 3. Note NOTE: During mounting, the metal part of the PROFIBUS DP connector is connected internally to the cable shield. When the bus cable connector is inserted into the module’s PROFIBUS port, a short connection between the shield and the FE/PE is created automatically. 32 709609 07/2011