Security Technical 9.2.5 91 System Points The follow system points are provided for monitoring security status on the SCADAPack E RTU: Security Information System Point Address Description Security Mode Analog Input 57600 0=None (read only) 1=AGA12 RTU 2=AGA12 Gateway AGA12 Mixed Mode Binary Input 50740 (read/write) Enabled / Disabled* * Only Disabled state can be written as per AGA12 rules Communication Performance Monitoring Performance Counter System Point Address Description (Analog Input) AGA12 Open Failures 57610 Session negotiation rejections (e.g. not a configured or authorized SCM) AGA12 HMAC Failures 57611 Frames where the verification signature doesn't match (e.g. content modified, frame corrupted, key mismatch) AGA12 ACK Timeouts 57612 Session open attempts where no reply was received within the timeout period AGA12 Frames Blocked 57613 AGA12 frames that couldn’t be delivered (e.g. no configured SCM address) AGA12 Frames Routed 57614 Successfully routed AGA12 frames AGA12 Frames Decoded 57615 Successful incoming frames correctly signed and decrypted AGA12 Frames Encoded 57616 Outgoing frames successfully delivered