Download PROFIBUS and PROFINET for Digital Dosing

Transcript
Module
Name
Data type
English (GB)
7.8 Alarms and warning
Description
18
FaultCode
5
Code for active pump alarm.
See event code in the table below.
19
WarningCode
5
Code for first active pump warning.
See event code in the table below.
All active warnings.
The belonging event code in parenthesis.
20
WarningBits
6
Byte 1
Bit 0: Backpressure low (211)*
Bit 1: Air bubbles (35)*
Bit 2: Cavitation (208)*
Bit 3: Discharge valve leakage (36)*
Bit 4: Suction valve leakage (37)*
Bit 5: -- reserved -Bit 6: Service now (12)
Bit 7: Service soon (33)
Byte 2
Bit 0: Low level in tank (206)
Bit 1: -- reserved -Bit 2: FlowControl cable breakdown (169)*
Bit 3: Bit 4: Bit 5: Flow deviation (17)*
Bit 6: Bit 7: -
* Requires FlowControlEnable bit in ControlModule to be set.
In case of a pump alarm or pump warning the modules
WarningCode and FaultCode will contain an event code for the
cause of the problem.
The complete list of possible alarm/warning codes from a DDA
pump is shown in the table below.
Alarm events will make the pump stop. Some of them require
acknowledgement of the alarm before the pump can be restarted.
This acknowledgement can come from the pump HMI or
PROFIBUS/PROFINET by usage of the ResetFault command.
The pump can only indicate one active alarm at a time, whereas
there can be many simultaneously active warnings. The complete
status of warnings can be read from the WarningBits module.
19