6.2 Detailed Descriptions of Monitoring Operations
Clear Button
This button clears the contents of the Machine Controller's RAM. When it is clicked, the following message
will be displayed for confirmation.
Œ If program write protection is set to Write Disable in the Setup Folder of the Environment Setting Dialog Box,
connection may not be possible the next time it is attempted. If this occurs, turn the power supply to the
Machine Controller OFF and then back ON.
Scan Time Display
The scan time values are displayed here. If a Scan Time Over occurs, it will be displayed in red showing an
error.
The Scan Time Over occurs if the current value or maximum value exceeds the setting value.
LED
Setting Value
Current Value
Maximum Value
High
Speed
Indicator color: Black
Monitor register: SW00004
Blue: Within the set range
Red: Over the set value
Monitor register: SW00005
Black: Within the set range
Red: Over the set value
Monitor register: SW00006
Low
Speed
Indicator color: Black
Monitor register: SW00010
Blue: Within the set range
Red: Over the set value
Monitor register: SW00011
Black: Within the set range
Red: Over the set value
Monitor register: SW00012
Setting Button
When this button is clicked, the Scan Time Setting screen in the Environment Setting Dialog Box is displayed
and the scan time can be changed.
6
Clear Button
When this button is clicked, the maximum value for the high-speed or low-speed scan is cleared.