Download user manual elevator control panel close loop dc mgset cqm1
Transcript
? Type in CLR-FUN-MONTR-MONTR. ? Make sure that POWER and RUN indicators on the CPU are on. Then you may turn the elevator back in service. 13.3. INPUT/OUTPUT MODULES: Output module (CQM1-OC222): Output modules are provided with 2AMP rated not removable relays. Those relays may become defective after some hundreds of thousands of operations or if their contacts are overloaded. (Relay part number: G6 D-1A-DC5) Output module (CQM1-OD213): The PLC output module includes 100ma 24VDC optocouplers. It also includes a protective pico fuse which can be damaged if the 120VAC is applied on the module (fuse replacement number: MCR03.5). See the graph below for t he exact position of the "F1 125V 3.5A" fuse. Output problems : ? If the red output led is "ON" but there is no voltage on the corresponding terminal; the relay may be in trouble. Replace the module. ? If the red output led is "OFF" but there is a voltage on the corresponding terminal, the relay contact may be "soldered". Replace the module. Relay positioning in the CQM1-OC222 module: 13-4