[1.14 - WATER SOLUT.] ~ [<EXPANSION>] ~ [CONFIG] ~
[CI_AI51 Type] : (Water Solution Analogue Input 51)
Default
Range
Modbus Address
4-20 mA
4-20 mA or 0-20 mA
%mw570
This parameter allows the user to select the type of transducer being installed.
[CI_AI52 Type] : (Water Solution Analogue Input 52)
Default
Range
Modbus Address
4-20mA
4-20 mA or 0-20 mA
%mw572
This parameter allows the user to select the type of transducer being installed.
[Stop Type] : (Stop Type)
Default
Range
Modbus Address
Ramp
Ramp or Wheel
%mw574
This parameter allows the user to select the stop type. At times ramp stop is not suitable for the pump being controlled so the user can
select Wheel which causes the motor to stop using the freewheel stop type.
Please note that the setting in this screen has priority over [1.7 APPLICATION FUNCT] [STOP CONFIGURATION] [TYPE OF STOP](Stt)
[Fault Ramp] : (Fault Ramp)
Default
Minimum
Maximum
Unit
Modbus Address
3.0
0.0
999.9
sec
%mw576
This parameter sets the ramp rate to be used when a fault occurs.
[Fault Hist] : (Fault History)
Default
Minimum
Maximum
Modbus Address
0
0
8888
%mw592
This parameter shows a history of application faults in a numerical format. A maximum of four digits will be displayed with the left most digit
giving the code for the oldest application fault and the right hand digit giving the code for the most recent application fault. The fault codes
are as follows:
1
2
3
4
5
6
7
8
Flow switch fault.
Flow rate fault
Analogue high pressure fault
Cavitation fault
Cycle fault
Minimum pressure fault
Low level fault
Digital high pressure fault
If this screen displays 3622 then the last two faults were flow rate, the fault immediately prior to these was a minimum pressure fault and
the oldest recorded fault was an analogue high pressure fault. The value in this screen is not write protected so may be reset to zero.
83