Download User Manual
Transcript
5 Trouble shooting Please contact the distributor if problems can not be solved by the trouble shooting below No 1 Problem description A. Input power absent Use Multi-meter to measure the input to see if diagnostics B. Low input it is normal or not. the UPS is in battery mode 3 No alarm but no output The UPS doesn’t start after 4 pressing On button 5 Solution No display on the LCD, no self- AC normal but AC indicator off, 2 Probable causes AC indicator blinking A. Input circuit breaker off. B. Input power connection problem Output connection problem A. time of pressing ON button is insufficient. A. Switch on input breaker B. Check the connection and re-do. Check the connection and re-do A. Press and hold On button for 1s B. Disconnect all loads and restart B. Overload Input AC is beyond normal range Pay attention to the backup time if the UPS is in battery mode Buzzer beeps twice every 6 second & LCD shows “output UPS overload Disconnect some loads A. Battery circuit breaker off or A. Switch On the breaker & check the battery overload” ”Fault indicator On and the LCD 7 shows “battery fault” Fault indicator on and the LCD 8 shows ”charger fault “ 9 Abnormal backup time poor connection connections B. Reverse battery connection B. Check the battery polarity C. Battery defective C. Contact distributor to replace the battery Charger defective Contact distributor A. Battery not fully charged B. Battery Bad A. Charge battery for 8 hours when AC is normal, then test the backup time again B. Contact distributor to replace battery A Check to see if there is wind blowing out Long beeps and fault indicator 10 on, the LCD shows from fans Over temperature inside UPS over-temperature B Move objects away from the UPS C Wait till the UPS becomes cool and restart the UPS Long beep fault indicator on and 11 the LCD shows “output short Output short circuit Eliminate the short circuit and restart the UPS Fault inside UPS Contact distributor circuit ” 12 Long beeps and fault indictor on and the LCD shows “rectifier fault”/“inverter fault”/“auxiliary power fault”/“output fault” 13 Abnormal sound or smell Fault inside UPS shut down the UPS immediately and Contact distributor Please provide the UPS model, SN when calling distributor for maintenance. - 26 -