Download Function Block - TKK Automation Technology Laboratory

Transcript
Function Blocks Instruction Manual
User Manual
Corresponding Configuration
Parameterization
AI BLOCK (LD302) :
TAG=LT-100
MODE_BLK.TARGET=AUTO
CHAR BLOCK (LD302) :
TAG=FY -100
MODE_BLK.TARGET = AUTO
X_UNITS= inH2O
Y_UNITS= gal
CURV_INPUTS=(0,40,80,100,120,160,200)
CURV_OUTPUTS=(0, 14.23, 37.35, 50, 62.64, 85.76, 100)
PID BLOCK (LD302) :
TAG=LIC -100
MODE_BLK.TARGET=AUTO
PV_SCALE=0 - 100 gal
OUT_SCALE=0 - 100%
265