Chapter 1
Installation/Wiring
I/O
3 Wire SNK Control Non-Reversing
Connection Example
Internal Supply (SNK)
Stop
01
02
Start
04
Internal Supply (SRC)
3 Wire SRC Control Reversing
11
P046 [Start Source 1] = 2,
t062 [DigIn TermBlk 02]
Stop
= 49 and t063 [DigIn
TermBlk 03] = 51
Start
A momentary input will
start the drive. A stop
Direction
input to I/O Terminal 01
will stop the drive as
specified by P045 [Stop
Mode]. I/O Terminal 03
determines direction.
3 Wire SNK Control Internal Supply (SNK)
Reversing
Stop
External Supply (SRC)
Stop
01
02
03
01
02
03
04
Start
Direction
+24V
Common
Each digital input draws 6 mA.
01
02
03
04
Start
Direction
Opto Output (1 & 2)(1)
t069 [Opto Out1 Sel]
determines Opto-Output 1
(I/O Terminal 17)
operation.
t072 [Opto Out2 Sel]
determines Opto-Output 2
(I/O Terminal 18)
operation.
When using Opto-Output
with an inductive load
such as a relay, install a
recovery diode parallel to
the relay as shown, to
prevent damage to the
output.
Analog Output(1)
t088 [Analog Out Sel]
determines analog output
type and drive conditions.
0-10V,
1k Ω minimum
0-20 mA/4-20 mA,
525 Ω maximum
Opto-Output 1
17
CR
+24V
19
Common
Each Opto-Output is rated 30V DC 50 mA (Non-inductive).
t088 [Analog Out Sel] = 0 through 23
The Analog Output Select jumper must be set to match the analog output signal mode set in
t088 [Analog Out Sel].
Common
14
+
16
(1) Feature is specific to PowerFlex 525 drives only.
44
Rockwell Automation Publication 520-UM001G-EN-E - September 2014