Each device or device type being emulated must have a
csv ‘profile’ file created and configured for it. The
Emulator requires a profile of registers, register names,
initial values and min/max values (for dynamic registers).
Without this profile all returned Modbus values will be zero.
•
A second computer configured with PMCS (see
requirements for PMCS) or similar Modbus master,
NativeCOM v5.02 (or later) and the required NativeCom
Generic Port Server license (included with the purchase of
the Emulator).
•
All hardware/software required to network the two PC’s
together for TCP/IP
•
No network ‘firewalls’ between the PC’s that block IP ports
502 and 9000~9256(default config, ports assignments can
be customized)
II. Modbus RTU/IP Specs:
The Emulator supports all the devices, functions codes and
register ranges of the GE PMCS Modbus servers:
Modbus types: RTU (all baud rates and interfaces) and TCP/IP
(any port, default 504)
Modbus TCP/IP hosts: Only 1 ModbusIP master connection
allowed per IP port, polling MUST be in a query/response pattern
(the same pattern as Modbus RTU). Multiple, simultaneous
queries on the same port are not supported with the current
version of the PMCS server or the PMCS Emulator.
Comports supported: Max 256 available to Windows OS
Modbus Function codes: 01, 02, 03, 04, 05, 06, 15, 16
Modbus address ranges: 1 ~ 247
ModbusIP port Ranges supported: 0 ~ 65535, default Comport
mapping starts at IP port 9000 (i.e. 9000+ Com 10 = 9010)
Modbus Exception responses: The Emulator does not support
automatic generation of Modbus exception codes however it does
support manual generation of all codes using the Emulator
‘Control Panel’.
Read/Write: Full write support of all data types and formats for a
PCMS system with the exception of ‘Array’ writes. Note: upon
2-8 Emulator use and configuration guide