Interfaces of the Device The maximum cable length depends on the baud rate used. Table 4-31 Baud rate CAN Baud rate Cable length 20 kBit/s 1000 m 125 kBit/s 500 m 250 kBit/s 250 m 500 kBit/s 100 m 1000 kBit/s 25 m 4.4.1.3 Termination Terminate the CAN bus at both ends by terminating resistors (120 Ohm). 4.4.1.4 Diagnostics LEDs Diagnostics LEDs are located at the rear of the operating device. The LEDs show the states of the bus system. Table 4-32 Functions of the CAN diagnostics LEDs Designation Color State Function SYS Green On Communication in progress Green Flashes cyclically Communication stopped Green Flashes irregularly Configuration is missing or contains errors Yellow Flashes cyclically Bootstrap loader active Yellow Flashes irregularly Hardware error / system error Red On CAN error Yellow On Transmission on CAN bus in progress COM 4.4.1.5 Diagnostics Interface (X6) To be able to use the diagnostics interface you need the System Configurator Software SyCon. You can obtain this software directly from Sütron electronic. The diagnostics interface is connected with the serial interface of the PC. 4.4.1.5.1 Figure 4-20 Pin Assignment 9 pin D-SUB male connector strip 4-27