5.Operation
ID
20
Group 1 Basic control parameter settings
Contents
Setting range
Unit
Standard value
Torque Command Filter 1
[TCFIL1]
1 to 4000
Hz
600
■ Low-pass filter to eliminate high frequency component included in the torque command.
Sets cutoff frequency.
◆ Automatically saved by Auto-tuning result saving.
◆ When Auto-tuning function is valid, this setting value is not applied.
◆ When Gain switching function is valid, select gain 1 and this setting value is applied.
◆ When Auto-tuning is valid, while system analysis function is active, this value is applied.
Setting range varies depending on the setting of the system parameter ID00 Control
Cycle.
(Torque command filter cannot be disabled)
Control Cycle
Setting value
Cutoff frequency
Same as the setting
1 to 2000[Hz]
value
Standard_Sampling
00
Standard Sampling
2001 to
2000[Hz]
4000[Hz]
High-freq_Sampling
Same as the setting
01
1 to 4000Hz
High Frequency Sampling
value
Use within 1 to 1000Hz with Model following control.
Use within 100 to 1000Hz with Model following vibration suppressor control.
21
Setting range
Unit
Standard value
Torque Command Filter Order
[TCFILOR]
1 to 3
Order
2
Sets order of the torque command filter.
The order is set within the setting range even if the cut off frequency of torque command filter is
changed by Gain switching.
5-38