Chapter 6: Enhanced Features
MLS300 Series User’s Guide
KOH Input
Water Input
Loop 1: Water Flow Control Loop
Loop 2: KOH Flow Control Loop
Loop 1 Input
Process Variable
Flow
Transducer
Loop 1 PID Output
Loop 2 Input
MLS300
Loop 2 PID Output
Process Variable
Motorized Control Valve 2
Motorized
Control
Valve 1
Serial
DAC
Serial
DAC
Mixture Output
Figure 6.8
Application Using Ratio Control
To set up this application, you would do the following:
150
1.
Adjust and tune loop 1 (H2O) for optimal performance
before implementing the ratio setup.
2.
Switch the controller to display loop 2 (KOH), and then
enter the three-key sequence (ENTER, then ALARM ACK,
then CHNG SP) and go to the first screen in Table 6.3.
3.
Follow the steps in Table 6.3 to configure ratio control.