Rate of change of frequency ANSI code 81R Protection functions Operation Protection function based on the calculation of the frequency variation, used to rapidly disconnect a source supplying a network or to control load shedding. The rate of change of frequency protection function is complementary to the under and overfrequency protection functions in detecting network configurations that require load shedding or disconnection. The function is activated when the "rate of change of frequency" df/dt of the positive sequence voltage is higher than a set point. It includes a definite (DT) time delay. The protection function operates if: b the positive sequence voltage is greater than 50 % of the rated phase-to-neutral voltage b the network frequency is between 42.2 Hz and 56.2 Hz for 50 Hz networks and between 51.3 Hz and 65 Hz for 60 Hz networks. Block diagram de51554 3 Characteristics Settings dfs/dt set point Setting range Accuracy (1) Resolution Drop out/pick up ratio Temporisation Setting range Accuracy (1) Resolution 0.1 to 10 Hz/s ±5 % or ±0,1 Hz 0.01 Hz 93 % 0.15 to 300 s ±2 % or -10 at +25 ms 10 ms or 1 digit Characteristic times (1) Operation time Overshoot time Reset time Pick-up < 150 ms (typically 130 ms) < 100 ms < 100 ms Inputs Designation Protection reset Protection inhibition Syntax Equations Logipam P81R_x_101 b b P81R_x_113 b b Outputs Designation Syntax Equations Instantaneous output (pick-up) P81R_x_1 b Tripping output P81R_x_3 b Protection inhibited P81R_x_16 b Invalid voltage P81R_x_42 b Invalid frequency P81R_x_43 b Positive df/dt P81R_x_44 b Negative df/dt P81R_x_45 b x: unit number. (1) Under reference conditions (IEC 60255-6) and df/dt < 3 Hz/s. SEPED303001EN - 01/2013 Logipam b b b b b b b Matrix b 209