Download 3 - Schneider Electric
Transcript
Metering functions Frequency Operation This function gives the frequency value. Frequency is measured via the following: b based on U21 or V1, if only one phase-to-phase voltage is connected to the Sepam b based on positive sequence voltage in other cases. Frequency is not measured if: b the voltage U21 (or V1) or positive sequence voltage Vd is less than 40 % of Un b the frequency f is outside the measurment range. The measurement of the frequency f' is calculated according to the same principle, from V'd or U'21 or V'1 2 Readout The measurements may be accessed via: b the Sepam display via the key b the display of a PC with the SFT2841 software b the communication link b an analog converter with the MSA141 option. Characteristics Main channels Rated frequency Range Resolution Accuracy (2) Display format Refresh interval 50 Hz, 60 Hz 25 to 65 Hz 0.01 Hz (1) ±0.01 Hz 3 significant digits 1 second (typical) Additional channels Rated frequency fn Range Resolution (1) Accuracy (2) Display format Refresh interval (1) On SFT2841. (2) At Unp, under reference conditions (IEC 60255-6). 36 50 Hz, 60 Hz 45 to 55 Hz (fn = 50 Hz) 55 to 65 Hz (fn = 60 Hz) 0.01 Hz ±0.05 Hz 3 significant digits 1 second (typical) SEPED303001EN - 01/2013