DVS-25HA probes is below the set point. If this isn't the case, the heaters will not turn on even if individual probe temperatures are below the set point. The figure below explains the operation of zoned heaters. Heating Heater turns on ON Heater turns off OFF HEATER DIFFERENTIAL Temperature HEATER OFFSET Set Point If the room temperature rises: - at Set Point - Heater Offset 1 (Zone 1) : Heater 1 turns off. - at Set Point - Heater Offset 2 (Zone 2) : Heater 2 turns off. If the room temperature falls: - at Set Point - Heater Offset 1 - Diff. 1 (Zone 1) : Heater 1 turns on. - at Set Point - Heater Offset 2 - Diff. 2 (Zone 2) : Heater 2 turns on. DVS-25HA.rev.06 51