DVS-25HA HUMIDITY COMPENSATION USING HEATER 1 Heater 1 can be used to reduce humidity levels under certain conditions. When the relative humidity is greater than the humidity set point, Heater 1 operates according to a timer cycle as long as Stage 2 fans are not running. When the humidity drops to the humidity set point - 3%, Heater 1 turns off. This feature is enabled by setting internal switch # 11 to ON. The alternative to using this feature is to compensate the Stage 1 minimum speed (see Ventilation Settings — only one of the two compensation methods can be used). Note that if zoned heaters are used, both heaters 1 and 2 are used to compensate humidity. Heater 1 operates according to timer settings Heater 1 turns off Heater 1 3% Relative Humidity Set Point Heater 1 operates according to timer settings as shown below: TIME ON ON OFF TIME OFF 54 DVS-25HA.rev.06 Relative Humidity