Installation Drawings Figure 49 UPS dimensions continued, center of gravity—side, top and bottom views 23.4" (595mm) See Detail A 3" (77mm) 9.2" (235mm) Power Cable Entry 21.26 x 7.87" (540 x 200mm) 28.3" (719mm) Bracket Centers Vent Screen 34.3" (871mm) Power Cable Entry 21.26 x 7.87" (540 x 200mm) 28.3" (719mm) TOP VIEW 0.8" (21mm) BOTTOM VIEW 39-1/2" (1000mm) Mechanical Stop Caster 8.9" (226mm) 1.4" (36mm) Detail A 31.5" (800mm) without Side Panels Vent Screen Front and Back Display Center of Gravity Front Front Center of Gravity 78.7" (2000mm) Dimension Y; See Pg. 2 1.56" (40mm) LEFT SIDE VIEW See Pg. 2 Dimension Z Dimension X OVERALL FRONT VIEW 31.8" (808mm) 1. All dimensions are in inches (mm). 2. 24" (610) minimum clearance above unit and 12" (305) rear clearance required for air exhaust and 36" (914) front access required for service. 3. Keep cabinet within 15 degrees of vertical. 4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 5. Unit bottom is structurally adequate for forklift handling. 6. Control wiring and power wiring must be run in separate conduits. 7. Only copper cables are recommended. See Page 2 8. All wiring is to be in accordance with national and local electrical codes. 9. See page 2 of 5 drawing: UAM02010B for weight table and centers of gravity for UPS at 208V. 10. See page 3 of 5 drawing: UAM02010C for weight table and centers of gravity for UPS at 480V. 11. See page 4 of 5 drawing:UAM02010D for weight table and centers of gravity for UPS at 600V. 12. See page 5 of 5 drawing:UAM02010E for weight table and centers of gravity for UPS with internal maintenance bypass. Refer to Tables 11 and 13 for Dimensions X, Y and Z in each Liebert APM model. 63 RIGHT SIDE VIEW UAM2010A Rev. 2 Liebert® APM™