Download LevelPRO Measurement Systems
Transcript
Operation Mode/Fault Alarm Setup 4. System Fault Alarm a. The alarm is triggered when any of the following actions occur. i. Diagnostic error: ii. An Input Scan Error occurs and the detector has a problem reading any of the following devices: Analog inputs Main Board Temperature Detector Analog input Detector RTD input b. The alarm clears when the error condition is cleared. 5. Current Output A at Minimum Alarm a. The alarm is triggered when the current output A value is below the minimum set value. b. The alarm is cleared when the current output A value is above the minimum set value. 6. Current Output A at Maximum Alarm a. The alarm is triggered when the current output A value is above the maximum set value. b. The alarm is cleared when the current output A value is below the maximum set value. 7. Current Output B at Minimum Alarm a. The alarm is triggered when the current output B value is below the minimum set value. b. The alarm is cleared when the current output B value is above the minimum set value. 8. Current Output B at Maximum Alarm a. The alarm is triggered when the current output B value is above the maximum set value. b. The alarm is cleared when the current output B value is below the maximum set value. 9. Current Output C at Minimum Alarm a. The alarm is triggered when the current output C value is below the minimum set value. b. The alarm is cleared when the current output C value is above the minimum set value. Thermo Scientific LevelPRO User Manual 4-11