Outstation ID
This is the DNP address of the outstation.
Event poll
This is the frequency, in seconds, the outstation will be polled for event data. Enter a
value of zero to disable event polling. The outstation must be configured to report
events as one of the class types.
Integrity poll
This is the frequency, in seconds, the outstation will be requested to send all data. Enter
a value of zero to disable integrity polling. NOTE: This does not included any data the
outstation has not configured to be reported.
Unclassed poll
This is the frequency, in seconds, the unclassed reads will be executed. Enter a value of
zero to disable unclassed reads. If one or more reads have not been configured this
timer is disabled. NOTE: All the enabled reads will be executed starting with the first one
in the list and ending with the last one in the list. The timer does not restart until all the
enabled reads have completed or timed out.
Operate mode
This selects the mode used to modify writable I/O objects. (10 and 40)
Class 1, 2, 3 unsolicited messages
Enable - Unsolicited messages are enabled for the class.
Disable - Unsolicited messages are disabled for the class.
No change - The outstation selects if unsolicited messages are enabled or disabled for
the class.
DNP display time
This determines how time values are handled.
If UTC is selected:
Time values from the outstations are not converted to local time.
Time values for internal alarms are converted from local time to UTC.
If local time is selected:
Time values from the outstations are converted to local time.
Time values for internal alarms are not converted from local time to UTC.
Page 540