Honeywell
OpenTherm Boiler Function
5.7
OpenTherm Boiler Function
Function
001-D
OpenTherm Boiler
Select OpenTherm Boiler Function. If this screen is
displayed, press
. If this Function is being configured
for the first time, the Configuration Menu is displayed. If
configuration of this Function has already been carried
out, set access level 3 first.
CONFIGURATION
Press
Configuration
to access the Configuration Menu.
Choose Yes using
Configure
Function
or
and then press
.
No
BOILER MAXIMUM RATING
Boiler
max rating
Enter the boiler maximum rating.
45kW
BOILER MINIMUM RATING
Boiler
min rating
30%
Enter the boiler minimum rating as a percentage of the
boiler maximum rating.
RESET COUNTERS
Reset counters
No
Choose Yes, for example when commissioning the
system, to reset all the hour counters and impulse
counters in the Function to zero. The current date is
automatically entered as the start date.