Features Operating modes
SETTINGS MENU
Timed override
delay off
0h
7.1.8
When the timed override input is opened, the Function
remains in day mode for the set time.
Holiday timed override input
The Function determines the mode of operation in the normal way when the timed
override input is opened. When the timed override input is closed, the Function goes
into holiday mode.
This feature may only be active if specified during configuration.
OPERATING DATA MENU
Timed override:
Holiday operat
7.1.9
The Function is in holiday mode because the timed
override input is closed.
Preheating
Preheating is the process of switching on the heating early, i.e. before the start of the
day period. This ensures that the room temperature has already reached the setpoint
temperature at the start of the day period. The required pre-heating time is
determined by the Function. The preheating time increases with increasing difference
between the setpoint room temperature during day mode and the actual room
temperature. A longer preheating time is also required if it is colder outside. A
minimum and a maximum preheating time can be set.
OPERATING DATA MENU
Preheat:
Day operation
The Function is in day mode as a result of preheating.
The measured room temperature is 20 °C.
Room temp
20°C
Outside temp
14°C
The measured outside temperature is 14 °C.
SETTINGS MENU
Minimum preheat
time
15min
The Function switches on prematurely by at least the set
time.
Maximum preheat
time
360min
The Function switches on prematurely by the set time at
a maximum.
AX5200SQ Modulating Boiler Sequence Controller (OpenTherm)