Download SYSDRIVE 3G3HV
Transcript
Chapter 2 Installation D Installing a Thermal Relay This Inverter has an electronic thermal protection function to protect the motor from overheating. If, however, more than one motor is operated with one Inverter or multi-polar motor is used, always install a thermal relay (THR) between the Inverter and the motor and set n033 to 0 (no thermal protection). In this case, program the sequence so that the magnetic contactor on the input side of the main circuit is turned off by the contact of the thermal relay. D Installing a Noise Filter on Output Side Connect a noise filter to the output side of the Inverter to reduce radio noise and induction noise. 3G3HV Power supply Noise filter Induction noise Signal line Radio noise AM radio Controller Induction Noise: Electromagnetic induction generates noise on the signal line, causing the controller to malfunction. Radio Noise: Electromagnetic waves from the Inverter and cables cause the broadcasting radio receiver to make noise. D Countermeasures Against Induction Noise As described previously, a noise filter can be used to prevent induction noise from being generated on the output side. Alternatively, cables can be routed through a grounded metal pipe to prevent induction noise. Keeping the metal pipe at least 30 cm away from the signal line considerably reduces induction noise. Power supply 3G3HV Metal pipe 30 cm min. Signal line Controller 2-25