Download User Manual - Ungerboeck Software
Transcript
CBECC-COM User Manual 2013 Version 1f Loop Temperature Control section Temperature Crtl: The method used to control the chilled water supply temperature. The options are Fixed, Scheduled, OutsideAirReset and WetBulbReset. o Fixed means that a constant temperature setpoint is used. o Scheduled means that the temperature is adjusted based on a user specified schedule. o OutsideAirReset means that the water supply temperature is adjusted based on the outdoor air temperature. o WetBulbReset reset means that the water supply temperature is adjusted based on the cooling load. Fixed Supply Temp: The supply water temperature setpoint for 'Fixed' temperature control 69