Notation There are 16 timers available in AC and DC models of 250 lines. Timers can be used as contact as well as coil. In Genie T stands for Timer and timer numbers are represented from 1 to 16. Thus T8 represents the eighth timer. We refer the value of the nth timer as Tn. Timer used as Contact . Normally open (Tn): In this type of contact TRUE value is valid. . Normally closed. (tn): In this type of contact FALSE value is valid. Timer used as Coil . Trigger Input (TTn): In timer functions trigger is required to start timer operation (Timer cycle). . Reset Input (RTn): Reset input is used to reset the current Timer value to zero. The Trigger contact is disabled and the block is ready for a new timer cycle. Note: If Reset and trigger become true simultaneously then the relay is reset and the timer does not run. Timing Genie allows different timing ranges. S - Time value is specified in seconds Maximum time is 999.9 S Resolution: 100 ms M: S - Time value is specified in minutes: seconds Maximum time is 99.59 M Resolution: 1s H: M - Time value is specified in hours: minutes Maximum time is 99.99 H Resolution is 1min Note: If Time value = 0 and Trigger is given then unpredictable operation may take place, this condition is shown as Program Error during program entry.