11. Network objects
11. 4. Logical Digital Output (LDO) Summary
Logical Digital Output (LDO) points are used for executing drive commands such as RUN/STOP and reset. The APOGEE® FLN P1 card
supports 16 different logical digital output points (15 among them are for drive control, one special point is reserved for maintaining
compliance). The values of logical digital output points can be modified by write point or memorize point commands. Release commands
will not cause the logical digital output points to automatically return to their pre-override values. LDO points do not support COV.
Logical Digital Output (LDO) Summary
Point
Number
22
24
26
29
40
41
42
43
44
45
48
49
59
68
69
94
97
98
Point
Name
CMD FWD.REV
CMD STP.STRT
EXT1.2 CMD
DAY.NIGHT
DO 1 COMMAND
DO 2 COMMAND
DO 3 COMMAND
DO 4 COMMAND
DO 5 COMMAND
DO 6 COMMAND
RST RUN TIME
RESET KWH
LOCK PANEL
FLN LOC CTL
FLN LOC REF
RESET FAULT
MBOX READ
MBOX WRITE
Factory
Default
FWD
STOP
Reserved
DAY
OFF (1)
OFF (1)
OFF (2)
OFF (2)
Reserved
Reserved
NO
NO
Reserved
AUTO
AUTO
NO
DONE
DONE
Slope
Intercept
0
0
ON (1)
Text
REV
RUN
OFF (0)
Test
FWD
STOP
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
NIGHT
ON
ON
ON
ON
ON
ON
RESET
RESET
DAY
OFF
OFF
OFF
OFF
OFF
OFF
NO
NO
1
1
1
1
1
0
0
0
0
0
FLN
FLN
RESET
READ
WRITE
AUTO
AUTO
NO
DONE
DONE
(1) If IO basic card (VW3A3201) has been inserted.
(2) If IO extended card (VW3A3202) has been inserted.
BBV10543 10/2010
33