MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC t = 250ms Î t1 > 250ms t2 = 250ms WARNING: if Reset is enabled, the input consecutive to those used by the functional block must be used. For example: If inputs 1 and 2 are used for the functional block, input 3 must be used for Reset. Power-on test: If selected, enables the power-on test of the device. This test requires activation and de-activation of the device in order to run a complete functional check and enable the Output terminal. This test is required only at machine start-up (power-on of the module). Filter (ms): Permits filtering of signals from the device. This filter can be set to between 3 and 250 ms and eliminates any rebounds on the contacts. The duration of the filter affects calculation of module total response time. With simultaneity: If selected, activates control of simultaneity between switching of signals from the device. Simultaneity (ms): Is active only if the previous parameter is enabled. Determines the maximum permissible time (msec) between switching of two different signals from the sensor. Enable Error Out: If selected reports a fault detected by the function block. English Item description: Permits insertion of a descriptive text of the function of the component. This text will be displayed in the top part of the symbol. 88 8540780 • 21st March 2014 • Rev.20