Setting
Description
Range
Default
Default Count
Number of times to consecutively repeat a
control code, applying the pulse on and pulse
off times to each control pulse repetition
(applies only to Control Codes of type Pulse On,
Pulse Off, Trip, or Close).
1 to 255
1
Default On Time
Default duration, in milliseconds, of an ON pulse
0 to 65535
0
Default Off Time
Default duration, in milliseconds, of an OFF
pulse
0 to 65535
0
Read Only Registers
Mapping settings are available on the Read Only Registers tab as shown in Table
109.
Table 109 Read Only Register Mapping Settings
Setting
Description
Range
Default
Address
The MODBUS address assigned to the point
0 to 65535
X
IED
System Point Identifier. Consists of Home
Directory and Point Name. Based on selected
DO point from the Point Picker. Read only.
N/A
System
Assigned
Identifier
Point Name
Text description of the point in the Digital Output
map. Based on selected DO point. Read only.
Up to 128
characters
Assigned IED
point name
Type
The point type. Read only.
DI, AI, AO, ACC
Assigned type
Data Format
The type of data polled
See Table 76
INT16
Point Value to
Use
The attribute of the point to be polled
Value
Frozen Value
Date and Time
Freeze Date and
Time
Value
Multiplier
Scale factor of the point (m of formula mx + b)
Full range of 64bit Float
1.0
Offset
Scale factor of the point (b of formula mx + b)
Full range of 64bit Float
0.0
Property settings are available in the lower pane of the Read Only Registers tab. The
configuration settings defined in
D400 Substation Data Manager Software Configuration Guide
119