Download D400 Substation Data Manager
Transcript
GE Energy Setting Description Range Default Interrogation Group The interrogation group used for reporting this information object. Not Used Group 1 … Group 16 Not Used Report Class Specify if spontaneous events for this object are reported as class 1 or class 2 messages. Applies to unbalanced mode and spontaneous events only. Class 1 Class 2 Class 1 Time Tag The type of time tag to use. None With Time Tag With CP56 Time Tag None Address Read only. N/A N/A IED System Point Identifier. Consists of Home Directory and Point Name. Based on selected DI point from the Point Picker. Read only. N/A System Assigned Identifier Point Name Text description of the point in the Binary Input map. Based on selected DI point. Read only. Up to 128 characters Assigned IED point name. Accumulator Type Specifies whether every change (transition) or every pair of changes (pulse) in the monitored accumulator point value increments the reported count. Pulse Transition Pulse Accumulator Return Type Specifies whether the running or frozen accumulator value is reported. Running Frozen Running Accumulator Freeze Specifies whether or not the master station is allowed to freeze the monitored accumulator point. Enabled Disabled Disabled Accumulator Clear Specifies whether or not the master station is allowed to clear the monitored accumulator point. Enabled Disabled Disabled Threshold Specifies the minimum change in accumulator value required to produce a spontaneous report or event. Only used when the Accumulator Return Type is Running. 0 to 1000000 1 Per-Point Settings 100 SWM0066–2.75–0, General