Download 505 Input/Output Modules
Transcript
Electrical Specifications (continued) Table A-16 Electrical Specifications for Relay Output Modules (PPX:505–5518) Model Number No. of Outputs Module Width PPX:505–5518 16 Single-wide Operating voltage range 10–250 VAC, 10–54 VDC Maximum rated load Inductive (per contact) (UL/CSA) (power factor = 0.4) (L/R = 7 ms) (L/R = 7 ms) 5 A @ 250 VAC 1 A @ 24 VDC; 0.25 A @ 125 VAC 5 A @ 240 VAC 3 A @ 24 VDC 2 A @ 48 VDC Resistive (per contact) Maximum Starter Size Size 5 @ 120 VAC Maximum rated load (per common) 8 A @ 250 VAC or 30 VDC* Minimum current 20 mA Temporary overload, one channel 8 A for 100 ms Relay contact resistance from connector 100 mW, typical Max. Delay time through module 10 ms on to off 10 ms off to on Typical bounce time 3 ms Max. module +5 V power from base 2.5 W Output fuse for, 1/common 8 A, 250 VAC 1.25 x .25, fast blow Contact type Dry, Form C Output type Non-latching, unprotected User power supply 20–28 VDC @ 200 mA Snubber values 0.1 µf, 330 Ω Typical number of operations Without snubbers With snubbers 300,000 cycles 2,000,000 cycles * 8 A with front access connector (2587705–8011) 5 A with side access connector (2587705–8010) A-20 Specifications SIMATIC 505 Input/Output Modules User Manual