Locate the PC Tool CU 3 in Start | Programs | Grundfos PC Tools and launch it.
The screen you will see depends on the tool setup chosen the last time the tool was
started. If you have just installed the tool it has the Standard Tool Setup. The Standard Tool Setup will work right away if you are using the COM 1 port of your PC and
your network connection is a GENIbus connection, see fig. 1, pos. 1. In this case a
screen image as shown in fig. 4 will appear (the number of CU 3 icons may differ
from your system), and you can skip to section “The main window”.
Tool setup for a
GENIbus connection
If your Operation Window wrongly shows no CU 3 icons or you get the warning message: “No contact to selected CU 3” then it is likely that the setup of your tool doesn't
match your physical connection (e.g. the COM port you are using).
Check the setup by opening the window File | Tool Setup | General Setup. Your
setup should be as shown below in fig. 3, but remember to select the COM port you
are actually using.
Click ‘Save’ to save your tool setup to the hard disk. After a few seconds the icons of
the connected units should appear. Consult section ‘Fault finding’ if it doesn't work.
Note: If connection type is changed from G100 to GENIbus the tool must be restarted.
TM01 8163 5199
Introduction
Fig. 3. General Setup Window with Standard Tool setup.
8