Bosch Phantom
Figure 9 – Connector Block, CT and Voltage
Attach the three voltage phase wires as indicated on the connection diagram according to
the labels on the connectors. Be extra cautious that no strands of the wire are unraveled and
thus outside of the connector which would then create the possibility for a phase-to-phase
short.
Attach the Line, Neutral and Ground connecting wires. These supply power for the Bosch
Phantom meter so when they become ‘live’ the unit will start operating.
Figure 10 – Connector Block, Power Supply
Note: To quick-start the unit and see something on the display the minimum connections
are:
[1] Neutral, [2] Line, [3] N Voltage Terminal, [4] A (or B or C) Voltage Terminal. In this
configuration only Volts will be displayed, for only the phase connected.
Installation and Operation Manual
10