306 Switch & Demux DEMUX-I (10061) Illustration DEMUX-I (BOOL) 81 TLA1 1 msec (1) A OA1 I OA2 OA1(81) OA2(81) Execution time 1.38 µs (when two outputs are used) + 0.30 µs (for every additional output). When all outputs are used, the execution time is 10.38 µs. Operation Input (I) value is stored to the output (OA1…OA32) selected by the address input (A). All other outputs are 0. If the address input is 0, negative or exceeds the number of the outputs, all outputs are 0. Inputs The input data type is selected by the user. Address input (A): DINT Input (I): INT, DINT, Boolean, REAL, REAL24 Outputs The number of the output channels (1…32) is selected by the user. Output (OA1…OA32): INT, DINT, REAL, REAL24, Boolean DEMUX-MI (10062) Illustration DEMUX-MI (BOOL) 82 TLA1 1 msec (1) A OA1 R OA2 OA1(82) OA2(82) L S I Execution time Standard function blocks 0.99 µs (when two outputs are used) + 0.25 µs (for every additional output). When all outputs are used, the execution time is 8.4 µs.