Download Preface - SAI Canarias
Transcript
660 modularized UPS user manual Table 4.1 Fault/warn Removal Problem Type Warning of charger module Fault/warning Solution BAT OVERCHARGED Power off the charger and contact customer service personal. BAT DISCONNECTED Check whether the external battery breaker is closed 2. Check whether the battery connection is normal or not BAT CGARGERFALL Power off the charger and contact customer service personal CHAEGER OFF Check whether charger is started or not CAN communication is abnormal Check whether the connecting line of corresponding charger module is connected well Disconnect the monitoring module 1. If the monitoring module is connected, please check whether the connecting line of monitoring module is connected well 2. Please insert monitoring module if the monitoring module is not connected. LCD ERRORVOLTSET Contact customer service personal to change the set. LCD ERRORCURRSET Contact customer service personal to change the set. EPO ACTIVE Check whether button of EPO is pressed or not, please check whether the screw in left side is fastened if it is not pressed. CHG FANLOCK Please contact customer service personal if the charger fan is damaged LINE PHASEERR Check whether the phase sequence of three-phase input line is correct or not NLOSS 1. Check the back terminal of module is in normal or not. 2. Check whether the terminal connected cabinet and module is in normal. - 45 -