4.8. Test Mode
4.9. Version
The test mode is used to simulate temperature and static pressure changes to verify the
controller’s performance. The temperature
probe and static pressure inputs are turned
off while the test mode is on. This mode is
automatically deactivated after 15 minutes of
inactivity or when you disable it.
This menu shows your controller’s version
number. This piece of information is useful
to get technical support.
1.Select:
»» 23. Controller Setup
»» 10. Version
1.Select:
»» 23. Controller Setup
»» 9. Test Mode
CC24-7 Elite
SETTINGS V X.X
Core V X.Xx
Test Mode
Test Mode Status
Temperature
Static Pressure
Date
Off
77.9°F
.080 “WC
2.Set the following parameters:
Test Mode Status — Select “Yes” to enable
the test mode,­ select “No” to exit from the
test mode.
Temperature — Enter the simulated room
temperature. *This parameter can only be changed
if the test mode status is enabled above.
Static Pressure — This is the current static
pressure level in the room. This value is
shown as a reference only; it cannot be modified. *This parameter is only shown if the static
pressure sensor is enabled (sec. 4.5).