Download Manual - Munters
Transcript
CC24-7 ELITE 11.2.1.Temperature Alarms Outdoor T° Compensation on Temp. Alarms The following diagrams explain how temperature alarms are detected: When the average room temperature exceeds the high temperature alarm setting (Set Point + Hi Offset), a high temperature alarm sets off. When the average room temperature decreases below the low temperature alarm limit (Set Point - Lo Offset), a low temperature alarm sets off. The critical temperature is the absolute maximum allowable temperature in the room. Outside Temperature Influence on Alarms: This feature avoids false alarms due to warm weather: the room temperature can exceed the Hi temperature limit in the case where the outside temperature is warm enough. The room temperature must remain equal or lower than Outside T°+ Outside Influence or lower than the Set Point + Hi Offset, whichever is higher but in every case, it must remain below the critical temperature, no matter what the outside temperature is. Room temperature Legend Outside temperature Temperature alarm High T° alarm limit Set Point + Hi Offset No alarm Outside temperature influence (no alarm) Out.T° Influence Outside temperature Set Point — Lo Offset Low T° alarm limit Time Temperature Alarm Settings 1.Select: »» 23. Controller Setup »» 5. Alarm Settings »» 1. Temperature Alarm limits Critical alarm limit Critical T° Low Offset Temperature High Offset Temperature Outside Influence Critical Temperature High Breaker Alarm 10.0°F 15.0°F 5.0°F 90.0°F 120.0°F 2.Set the following parameters: Low High Temperature Offset — The Hi and low offsets are the number of degrees below and above the set point at which a temperature alarm sets off. The low temperature limit ranges from 20°F to 0.5°F (11.1 to 0.3°C) below the set point (Lo Offset). The high temperature limit ranges from 0.5°F to 35°F (0.3 to 19.4°C) above the set point (Hi Offset). Outside Influence — The outside temperature influence is the number of degrees that are added to the outside temperature to avoid false alarms on warm days. Refer to the previous diagram. Critical Temperature — The critical temperature is the absolute maximum temperature that is allowed in the room. High Breaker Alarm — If the temperature of the main breaker is monitored by a probe, set the probe temperature over which a breaker temperature alarm must sound. *Accessible if the breaker’s monitoring function is enabled in section 4.5. Install the breaker’s probe close to the breaker box, not inside the box! CC24-7 ELITE rev.23 51