Download Ladder Logic User Manual
Transcript
Example: The temperature regulation of the house in the previous example can be improved by using a PI controller. If the window is opened on a cold day, a positive error results between the room temperature and the setpoint (i.e. the room is cold). The error accumulates in the integration term and as this term gets larger the output of the controller increases. As a result of the increase in the controller output, the room temperature increases until the setpoint is reached. When the setpoint is reached, the error and all the subsequent errors are zero and the integration term becomes a constant. PI control has eliminated the steady-state error that results when a disturbance is encountered by a P controller. Process Value Response process value setpoint t1 Controller Output Response time output ms t1 time Figure 3: Proportional-Integral Controller Response As a further illustration, assume that the window is now closed. Since a source of heat loss has been eliminated, the temperature rises above the 21°C setpoint producing negative errors. Summing these negative errors into the integral term decreases the output of the controller. The temperature then falls until the setpoint is reached, at which point the error and all subsequent errors are zero. When this occurs, the integral term ceases to decrease and becomes constant. The output of the controller is constant and the room temperature remains at the setpoint. Steady-state error has been avoided. Figure 3 is representative of the typical response of the process and the PI controller to a disturbance. The steady-state error in Figure 2 is not characteristic of the process response when regulated by a PI controller. A novel (though not theoretically correct) way of viewing integral action is that it emulates the resetting of the setpoint. To see what is meant by this, consider that the occupant of the house in the previous example has found that the room temperature is below the desired level. The occupant is a P controller and regulates the temperature. Rather than checking for an open window, the occupant raises the thermostat setting every five minutes until the temperature is 21°C. The five minute period is the setpoint reset time, hence the naming of the parameter T in equation 3. It is important to understand that in a PI controller the setpoint is not altered. The integral term takes this "setpoint resetting" into account. TelePACE PID Controllers User and Reference Manual 10