Step 1
5
Read the Precautions and General Information
Qualified Personnel
!
ATTENTION: Only qualified personnel familiar with adjustable
frequency AC drives and associated machinery should plan or
implement the installation, start-up and subsequent maintenance of the
system. Failure to comply may result in personal injury and/or
equipment damage.
Personal Safety
!
!
!
!
ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged before performing any
work on the drive. Measure the DC bus voltage at the following points
(refer to pages 28 through 30 for locations):
• +DC and -DC terminals of the Power Terminal Block
• +DC terminal of the Power Terminal Block and the chassis
• -DC terminal of the Power Terminal Block and the chassis
The voltage must be zero for all three measurements.
ATTENTION: Risk of injury or equipment damage exists. DPI or
SCANport host products must not be directly connected together via
1202 cables. Unpredictable behavior can result if two or more devices
are connected in this manner.
ATTENTION: The drive start/stop/enable control circuitry includes
solid state components. If hazards due to accidental contact with
moving machinery or unintentional flow of liquid, gas or solids exist,
an additional hardwired stop circuit may be required to remove the AC
line to the drive. An auxiliary braking method may be required.
ATTENTION: Loss of control in suspended load applications can
cause personal injury and/or equipment damage. Loads must always be
controlled by the drive or a mechanical brake. Parameters 600…611 are
designed for lifting/torque proving applications. It is the responsibility
of the engineer and/or end user to configure drive parameters, test any
lifting functionality and meet safety requirements in accordance with
all applicable codes and standards.
Publication 20B-IN019C-EN-P