Download iDrive - Drives Direct
Transcript
Chapter 3 Environment description and installation 3.3.4 Safety and EMC: Good wiring practice IP20 models L1 L2 415V 50Hz 3-phase + N Power supply * 10mm L3 N E/Ground 2 4mm2 BACK PLATE (paint/coating free) L1(L) L3(N) PE iDrive EDX-220-21-E (for example) P N T1 T2 Optional ferrite choke, only required if motor cable is very long. Note: For very long cables an ACR should be used T3 PE 4mm2 ENCLOSURE Brass earth studs fixed through back plate and secured with shake-proof washers. NB. Both ‘PE’ terminals must be linked to back plate with 4mm2 (min) cable as shown. ** * NOTE 1 External earth / ground conductor if used. Enclosure (& backplate) must be connected to main earth system by single 10mm2 c.s.a. copper conductor to conform to BS7671 Earth / ground cables connected through isolator Local Isolator ** NOTE 2 Armoured or screened cable, 3C or 4C. Screen connected at all ends as shown. Motor Note: Power supply side ancillary equipment not shown in this diagram, for clarity. 3-11 ** Screen / armour must be connected as shown at each end of cable sections. If motor connection box is plastic, screen must be secured to the metal frame of the motor.