Download 3500 Process Controller HA027988_15_3500
Transcript
3500 Series Controllers 10.3.2 User Manual Single Isolated Logic Output This provides isolation from other IO and should be used, for example, in applications where the sensor and the output device may be at supply potential. It is only available as a time proportioning or on/off output. List Header - Mod Sub-headers: xA Name Value Parameter Description Press to select Default or to change values Access Level Ident Channel type Logic Out Logic output L3 R/O IO Type To configure the function of the relay OnOff On off output Conf R/O L3 Sets the sense of the logic output. This only applies if the output is configured as OnOff No Non inverted. Output off (logic 0) when PID demand off. For control this is when PV>SP. Output on (logic 1) when PID demand off. For control this is when PV<SP. This is the normal setting for control. Yes Inverted. Output off (logic 0). For an alarm this is when the alarm is active. Output on (logic 1). For an alarm this is when the alarm is in-active. This is the normal setting for alarms. Off The output will drive to 'electrical low' value regardless of the 'Invert' parameter. On The output will drive to 'electrical high' value regardless of the 'Invert' parameter. Cont The output will assume a status according to how it is driven 0 1 Off (if ‘Invert’ = ‘No’) On (if ‘Invert’ = ‘No’) L3 R/O Output off (if ‘Invert’ = ‘No’) Conf R/O L3 Invert SbyAct See also section 8.2.1. Standby action. Determines the output action when the instrument is in Standby Mode. Time Prop Time proportioning output Meas Value Current state of the output PV Normally wired to the output of a 0 function block such as PID output 1 to control a plant actuator Status Module status See note 2 - section 10.3.1 OK Conf R/O L3 Off Output on (if ‘Invert’ = ‘No’) Alterable if not wired Normal operation Conf R/O L3 R/O The next six parameters are only shown when ‘IO Type’ = ‘Time Prop’ outputs CycleTime To switch the output on and off See also within the set time period. section 8.2.2. Applies only to Time Proportioning outputs. Off or 0.01 When Off is selected the Min OnTime to 60.00 algorithm will run. seconds When set to any value the CycleTime algorithm will run. The minimum time (in seconds) that the logic output is on or off. Applies only to Time See also section 8.2.2. Proportioning outputs and is only available when ‘Cycle Time’ = Off Auto 0.01 to 150.00 seconds If set to Auto the minimum on time will Auto be 110mS. If the logic is used to control an external relay, Min OnTime should be set to a minimum of (say) 10 seconds to prevent the relay from switching too rapidly. Res’n Display resolution. This sets the number of decimal places displayed by Disp Hi and Disp Lo parameters XXXXX XXXX.X XXX.XX XX.XXX X.XXXX No decimal points One decimal point Two decimal points Three decimal points Four decimal points XXXXX Conf Disp Hi/Lo Maximum/minimum output demand signal 0.00 to 100.00 100.00 L3 Range Hi/Lo Electrical output high/low 0.00 to 100.00 These parameters allow high and low limits to be applied to the output against a set limit of the output demand signal from the PID loop. See also section 10.4.3. Meas Value The current status of the digital output. 0 1 Min OnTime Part No HA027988 Issue 15 Jun-13 On (unless Invert = Yes) Off (unless Invert = Yes) Off L3 L3 L3 L3 R/O L3 101