Download OPERATION MANUAL
Transcript
Section 14-1 Remote I/O Communications Characteristics First, the Network is divided into two groups: Master A and the Slaves in remote I/O communications with it and Master B and the Slaves in remote I/O communications with it. Slave A Group A Group B Master A Master B Slave B Slave C Slaves in remote I/O communications with Master A Note Slave D Slave E Slave F Slaves in remote I/O communications with Master B Although in the above diagram the Slaves are separated into two groups for convenience, the actual physical positions in the Network are irrelevant. Next, we can refer to the previous equations and calculate the communications cycle time for each group as if they were separate Networks. Group B Group A Master B Master A Slave A Slave B Slave C Group A communications cycle time: TRM-A Slave D Slave E Slave F Group A communications cycle time: TRM-B In Networks with two Masters, the communications cycle time for the entire Network will be the sum of the communications cycle times for the groups. TRM = TRM-A + TRM-B Although this example shows only two Masters in the Network, the total communications cycle time for any Network can be calculated by dividing it into groups and adding the communications cycle times of all groups. 14-1-4 System Startup Time This section describes the system startup time for a Network operating with the scan list enabled. The system startup time is the delay from the time that the Master Unit is turned ON until remote I/O communications begin. Here, we assume that the scan list is enabled and that remote I/O communications are set to start automatically at startup. System Startup Times The following table shows the system startup times for two cases. In the first case, the Master Unit starts up just after all of the Slaves’ power supplies are turned ON. In the second case, the Master Unit is restarted while communications are in progress. Case Slave’s indicator status The Master is started just after Slave startup. Just the Master is restarted. The NS indicator is OFF or flashing green. The NS indicator is flashes red while the Master is OFF. --- Just the Slaves are restarted. System startup time 6 seconds 8 seconds 10 seconds 233