5. The Hold Current Output at FAULT LOW command allows you to
hold the current output at the FAULT LOW level (3.6 mA or less).
Press the right arrow to execute the command or the down arrow to
continue to the next menu item.
Hold current outputs
at FAULT LOW
Exit this menu.
NEXT EXECUTE CMD
Figure 7–22.
6. The Hold Current Output at FAULT HIGH command allows you to
hold the current output at the FAULT HIGH level (20.8 mA or
greater). Press the right arrow to execute the command or the down
arrow to continue to the next menu item.
Hold current outputs
FAULT HIGH
Exit this menu.
NEXT EXECUTE CMD
Figure 7–23.
7. Enter the value (in percentage) of the midrange current output hold
value. The default value is 50.00%. Press the down arrow to move to
the next menu item.
Current output
hold mode value
50.00% of scale
NEXT
Figure 7–24
8. Press the right arrow to execute the Hold Current Output command to
hold the current output at the midrange value you specified in the
previous step. Press the down arrow to continue to the next menu item.
Hold current output
at 50.00% of scale
Exit this menu.
NEXT EXECUTE CMD
Figure 7–25.