Download - Control Synergy
Transcript
FreeWave Technologies HT Ethernet Addendum 900MHz V1.0h Setup: To program the modem, proceed as described in the Main Manual, with the following exceptions: • • • Capital U on the diagnostics port brings up the setup menu. You must use the diagnostic port (there's no RS232 Data Port in this modem) You must select the following settings. Setup Menus NOTE: The Baud Rate setting is neither the over the air data rate of the Radio Link, nor the data rate of the Ethernet 10Base-T connection to the LAN. This Baud Rate strictly sets the protocol internal to the Modem, between the Ethernet Interface and the RF modem. Menu 1, SET BAUD RATE Modem Baud is 1382400 (0) 230,400 (1) 115,200 … (9) 1382.4KB (A) Data, Parity (B) MODBus RTU (C) RS232/485 (D) Setup Port (E) TurnOffDelay 0 (F) FlowControl Must be “9” (1382.4Kbps) 0 0 0 2 TurnOnDelay 0 1 Must be "0" (Default) Must be "0" (Disabled) Must be "0" (TTL) Must be "2"* (Diagnostics port used for Set-up) No effect "0" (Default for both) Must be "1" (CTS flow control) Menu 1, Submenu F Ethernet/IP Radio Setup (0) (1) (2) (3) (4) (5) (6) (7) (8) Ethernet Mode Half/Full Duplex Slave IP Stack Slave UDP Mode IP Address Port Address IP Address 2 Port Address 2 MAC Filter 0 1 0 0 0 255.255.255.255 4131 255.255.255.255 6535 Must be set to "1"* Select either, depending on your network Must be set to “1” Used for diagnostics only Default Port Address 0 disables internal MAC filter. 1 enables. *NOTE: Once the "Ethernet Mode" setting is set to 1 (Menu 0, Submenu F, Option 0), the "Set-Up Port" (Menu1, option D) can no longer be changed. Therefore, it is important to ensure the "SetUp Port" is set at "2", prior to enabling the "Ethernet Mode". LAD0013AB Rev H 6 of 11