IM02602004E
ETR-4000
High Set Restricted Ground Fault Protection 87GDH
Elements
87GDH[1] ,87GDH[2]
Similar to the unrestrained phase differential protection, unrestrained ground differential protection functions are
provided for a high ground differential current.
IdG/Ib
87GDH
Trip Range
IdG[Ir2]
Slope2
IdG min
Operating Range
IdG[Ir1]
IdG[Ir0]
Slope1
Ir1= 2 x Ib
Ir2= 10 x Ib
Unstabilized High Set Differential Protection Step 87GDH.
320
High-Set /
Unrestrained Restricted
Ground Fault: Pickup
value of the ground
differential current
based on the rated
current.