Download Instruction Manual
Transcript
IM02602004E ETR-4000 High Set Restricted Ground Fault Protection 87GDH Elements 87GDH[1] ,87GDH[2] Similar to the unrestrained phase differential protection, unrestrained ground differential protection functions are provided for a high ground differential current. IdG/Ib 87GDH Trip Range IdG[Ir2] Slope2 IdG min Operating Range IdG[Ir1] IdG[Ir0] Slope1 Ir1= 2 x Ib Ir2= 10 x Ib Unstabilized High Set Differential Protection Step 87GDH. 320 High-Set / Unrestrained Restricted Ground Fault: Pickup value of the ground differential current based on the rated current. www.eaton.com Ir/Ib
Related documents
MRA4 HighPROTEC
Eton 4000 Plus Instruction manual
MRA4 HighPROTEC - DSF Technologies
SonicWALL TZ 170 10 Node with Comprehensive Gateway Security
SonicWALL TZ 170 10 Node
Metering Devices, Protective Relays, Software and Connectivity
User Manual - Neri Group
Advanced Modular Calibrator DPI 620 Brochure - Cole
Advanced Modular Calibrator and HART
SE-AM-19 - Declaration Account Submission via eFiling
RL-H2Sa
RL-H1Sa - GeoShack
DELL Force10 S6000
Istruzioni per l`uso NJ1 e
Crystal Touch: Single Touch
Seagate, part 2 F3 architecture Drive families: Barracuda 7200.11
service manual for hoist control device
Crystal Touch: Single Touch User`s Manual
Crystal Touch User`s Manual
Foz do Iguaçu - PR
SMOS End-to-end Performance Simulator 4.0 User`s Manual