IM02602004E ETR-4000 High Set Restricted Ground Fault Protection 87GDH Elements 87GDH[1] ,87GDH[2] Similar to the unrestrained phase differential protection, unrestrained ground differential protection functions are provided for a high ground differential current. IdG/Ib 87GDH Trip Range IdG[Ir2] Slope2 IdG min Operating Range IdG[Ir1] IdG[Ir0] Slope1 Ir1= 2 x Ib Ir2= 10 x Ib Unstabilized High Set Differential Protection Step 87GDH. 320 High-Set / Unrestrained Restricted Ground Fault: Pickup value of the ground differential current based on the rated current. www.eaton.com Ir/Ib