Download Varispeed E7

Transcript
Output Signal Level During Multi-Function Analog
Output
Min. Access
Unit Level
10 V: Max. frequency
(0 to + 10 V possible)
0.01
%
A
64H
0.01
%
A
65H
(Cannot be output.)
-
A
66H
Cooling fan Monitors the total operating time
U1-40 operating
of the cooling fan. The time can (Cannot be output.)
time
be set in 02-10.
1
hr
A
68H
Constant
Number
Name
U1-37
PI output
volume
PI control output
Given as maximum frequency/
100%
U1-38
PI command
PI command + PI command bias
Given as maximum frequency/
100%
Description
10 V: Max. frequency
MEMOBUS
Register
Shows MEMOBUS errors.
MEMOBUS
U1-39 communications error
code
1: CRC error
1: Data length error
Not used
(always 0)
1: Parity error
1: Overrun error
1: Framing error
1: Timeout
Not used
(always 0)
* The unit is set in o1-03 (frequency units of reference setting and monitor).
5-38